The conductive VIASOL coating systems reliably and immediately transport the electro-static charges away from the source; horizontally as well as vertically.
Universal VIASOL voltex and Universal ESD are tailored to the respectively required voltage ranges and the typically arising loads. Strict monitoring in production ensures an unchanging product quality, which is decisive in that environment.
System information
multi-layered floor coating systems - requirements for conductive floors:
1) explosion protection
2) electro-static protection
Explosion protection
VIASOL UNIVERSAL voltex / VIASOL PERM conductive / VIASOL WHG conductive N and other systems
charges need to be conducted safely and quickly
Directive BGR 132 (DIN EN 1081)
Resistance to ground RE ≤ 108 Ω
(for explosives RE ≤ 106 Ω)
The electrically conductive coating system for explosion-protected zones and all areas where electro-static charges are to be avoided
System thickness approx. 2-4 mm
ESD areas = EPA (Electrostatic Protected Area):
VIASOL UNIVERSAL ESD (EP) / VIASOL UNIFLEX ESD (PU) / VIASOL PERM CONDUCTIVE / ESD and other systems
Charges must be conducted within certain resistance ranges
DIN EN 61340-5-1 (replaces DIN EN 100 015)
Resistance to ground RE < 109 Ω or
floor as primary grounding measure
System resistance (human/shoe/floor)
7,5 x 105 Ω (750 kΩ) ≤ RS ≤ 3,5 x 107 Ω (35 MΩ)
The electrically conductive coating system for pure rooms, protection of persons and all areas that require ESD-provisions.
System thickness approx. 2-4 mm